What are Approach and Arc Flash Boundaries
NFPA 70E has developed requirements to reduce the risk of injury to workers due
to shock and arc flash hazards. There are three shock approach boundaries
(limited, restricted and prohibited) required to be observed in NFPA 70E 2000.
The limited, restricted and prohibited approach boundaries are based on the
voltage of the energized equipment. Also, NFPA 70E 2000 requires that before a
worker approaches exposed electric conductors or circuit parts that have not
been placed in a safe work condition, a flash hazard assessment must be
performed. Until equipment is placed in a safe work condition (NFPA 70E 2000
Part II 2-1.1.3), it is considered live. It is important to note that conductors
and equipment are considered live when checking for voltage while putting
equipment in a safe work condition. The flash hazard analysis should determine
the flash protection boundary (FPB) and level of personal protective equipment
(PPE) that the worker must wear. The flash protection boundary is based on
voltage, the available fault current and the time it takes for the upstream
protective device to operate and clear the fault. The boundaries are summarized
below:
Limited Approach Boundary
NFPA 70 defines Limited Approach Boundary as: A shock protection boundary to be
crossed by only qualified persons (at a distance from a live part) which is not
to be crossed by unqualified persons unless escorted by a qualified person. The
limited approach boundary is the minimum distance from the energized item where
unqualified personnel may safely stand. No untrained personnel may approach any
closer to the energized item than this boundary. The boundary is determined by
NFPA 70E Table 2-1.3.4 and is based on the voltage of the equipment (2000
edition). A qualified person must use the appropriate PPE and be trained to
perform the required work to cross the limited approach boundary and enter the
limited space.
Restricted Approach Boundary
A shock protection boundary to be crossed by only qualified persons (at a
distance from a live part) which, due to its proximity to a shock hazard,
requires the use of shock protection techniques and equipment when crossed. To
cross the Restricted Approach Boundary into the Restricted Space, the qualified
person, who has completed required training, must wear appropriate personal
protective equipment (PPE). Also, he must have a written approved plan for the
work that they will perform and plan the work to keep all parts of the body out
of the Prohibited Space. This boundary is determined from NFPA Table 2-1.3.4
(2000 Edition) and is based on the voltage of the equipment.
Prohibited Approach Boundary
A shock protection boundary to be crossed by only qualified persons (at a
distance from a live part) which, when crossed by a body part or object,
requires the same protection as if direct contact is made with a live part. Only
qualified personnel wearing appropriate personal protective equipment (PPE),
having specified training to work on energized conductors or components, and a
documented plan justifying the need to perform this work may cross the boundary
and enter the Prohibited Space. Therefore, personnel must obtain a risk
assessment before the prohibited boundary is crossed. This boundary is
determined by NFPA 70E Table 2-1.3.4 (2000 Addition) and is based upon the
voltage of the equipment.
Flash Protection Boundary
The Flash Protection Boundary is a safe approach distance from energized
equipment or parts. NFPA 70E establishes the default flash protection boundary
at 4 feet for low voltage ( < 600V ) systems where the total fault exposure is
less than 5000 amperes-seconds (fault current in amperes multiplied by the
upstream device clearing time in seconds. NFPA 70E also allows the Flash
Protection Boundary to be calculated. In some instances, calculations may
decrease the boundary distance. Persons crossing into the flash protection
boundary are required to wear the appropriate PPE as determined by calculating
methods contained in NFPA 70E. In addition, a qualified person must accompany
unqualified persons. The boundary is defined as the distance at which the worker
is exposed to 1.2 cal/cm2 for 0.1 second. IEEE Std 1584 - 2002 details the
procedure and needed equations for arc flash calculations. The equations are
used to calculate the incident energy and flash boundary. The IEEE procedure is
valid for voltages ranging from 208V volts to 15kV with gap ranges between 3 mm.
and 153 mm.
|