|
During last years different procedures have been proposed to calculate
electrical arc incident energy, flash boundary limits and provide with flame
resistant personal protective equipment recommendations.
The procedures include the IEEE Standard 1584, IEEE Guide for Performing
Arc-Flash Hazard Calculations, NFPA 70E Standard for Electrical Safety
Requirements for Employee Workplaces 2004 edition. At ITU worker safety is our
main goal, therefore, our engineers look at the results of these approved
methods, and choose the most conservative data... meaning we use the data that
provides the most practical protection to the worker. Workplace Safety is our
goal!
All methods are based on testing performed and calculations conducted for
selected range of prospective fault currents, system voltages, physical
configurations etc. The methods caution they are suitable for estimating arc
flash hazards only, and actual cases experienced in the field can be expected to
vary from the predicted values.
Selecting an appropriate method for incident energy determination is confusing
and difficult. Comparison of the above methods shows varying computed values for
incident energy The IEEE Standards method based on empirical equations
developed through multiple tests of varying fault scenarios appears to be the
most accurate one. It is applicable for systems with:
- Voltage of 208 to 15,000 volts
- Bolted fault current of 0.700 to 106 KA
- Grounding variations
- Open air or equipment enclosures of commonly available sizes
- Gaps between conductors of 13mm to 152 mm (0.5 to 6 inches)
|
Still, the procedure is limited to three phase arcing faults and therefore is
not applicable for unbalanced arcing fault studies. Duke's heat flux calculator
does the job for single phase arc fault in air but requires arc current input.
The input arcing current, dependent on the geometry, prospective bolted fault
current, voltage, has to be calculated by other means in advance.
The IEEE paper "Predicting Incident Energy to Better Manage the Electric Arc
Hazard on 600-V Power Distribution Systems" of the IEEE Transactions on Industry
Applications Vol. 36, No. 1, January/February 2000 used for the NFPA 70E
calculation method compared the measured three phase results with the calculated
results given for single phase arcs. It reported that, "three-phase test values
of maximum incident energy for the open arcs were from 2.5 to 3 times the values
predicted by the single-phase models. Three-phase test values of maximum
incident energy for the arcs in the cubic box were 5.2 to 12.2 times the values
predicted by the single-phase models".
Fuses and instantaneous circuit breaker will open in less than quarter of cycle
(4 ms) when subjected to high short circuit currents usually observed in 3 phase
symmetrical bolted case. The criteria is that the SC current exceeds let through
limit specified for a particular protective device. Prospective fault current
will never reach there maximum and exercise full incident energy potential when
the criteria is met.
The problem with unbalanced fault currents is that they are lower than 3 phase
fault currents. Therefore, circuit protection devices may not necessary limit
let thru energy and will require more time to clear the fault. Even 3 phase
faults may translate into unbalanced fault when one fuse opens before the
remaining fuses melt. For safety reason, it makes sense to analysis both three
and single phase / unbalanced cases and use the highest calculated incident
energy value in sizing personnel protective equipment.
|